It is used in medium and low gas pipeline system, as pressure adjustment and pressure stabilization equipment for residential district, industrial/commercial consumers and direct-fired equipment.
Applicable medium
Natural gas, Manufactured gas, Liquefied petroleum gas,and other gases.
Technical Parameters
Maximum Inlet Pressure P1max:4 bar
Inlet Pressure Ranges P1:0.2-4 bar
Outlet Pressure Ranges P2:0.01-0.3 bar
Accuracy Class: AC5
Lock up Pressure Class:SG10
Working Temperature:-20~60°C
Features
Modularization Structure Design
Easy Installation and Maintenance
Easy Pressure Enactment
Fast Response,Big Flow Capability
Balanced Valve Core Structure
High-Precision Pressure Adjustment
Connections
Flange Connect DN50、DN80、DN100、DN150、DN200
Flange Grade PN1.6 MPa
Overall Dimension
Regulator TYPE |
Main Dimension |
Inlet/Outlet Flange |
|||
L | H | H1 | D | ||
RTZ-50SN | 250 | 640 | 108 | 330/436 | DN50 |
RTZ-80SN | 300 | 650 | 118 | 330/436 | DN80 |
RTZ-100SN | 350 | 800 | 148 | 436/510 | DN100 |
RTZ-150SN | 450 | 900 | 193 | 436/510 | DN150 |
RTZ-200SN | 450 | 900 | 210 | 436/510 | DN200 |
Flow Capacity Table for 50SN (m³/h)
Outlet Pressure (bar) |
Inlet Pressure (bar) | |||||||||||||
0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 1.0 | 1.3 | 1.5 | 1.8 | 2.0 | 3.0 | 4.0 | |
0.02 | 192 | 240 | 280 | 315 | 345 | 375 | 400 | 450 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.03 | 188 | 237 | 277 | 313 | 344 | 374 | 400 | 450 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.05 | 178 | 230 | 272 | 310 | 340 | 371 | 399 | 450 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.08 | 162 | 220 | 264 | 303 | 337 | 368 | 396 | 448 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.1 | 149 | 210 | 258 | 298 | 333 | 365 | 394 | 447 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.15 | 108 | 186 | 240 | 285 | 324 | 357 | 389 | 445 | 517 | 562 | 630 | 675 | 900 | 1125 |
0.2 | — | 155 | 220 | 270 | 312 | 348 | 381 | 440 | 517 | 562 | 630 | 675 | 860 | 1100 |
0.25 | — | — | 195 | 250 | 297 | 337 | 373 | 435 | 515 | 562 | 630 | 675 | 790 | 990 |
0.3 | — | — | 162 | 230 | 280 | 324 | 362 | 430 | 513 | 562 | 630 | 650 | 790 | 950 |
Flow Capacity Table for 80SN(m³/h)
Outlet Pressure (bar) |
Inlet Pressure (bar) | |||||||||||||
0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 1.0 | 1.3 | 1.5 | 1.8 | 2.0 | 3.0 | 4.0 | |
0.02 | 200 | 374 | 435 | 489 | 538 | 582 | 624 | 700 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.03 | 292 | 369 | 432 | 487 | 536 | 581 | 623 | 700 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.05 | 277 | 358 | 424 | 481 | 532 | 578 | 621 | 700 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.08 | 252 | 341 | 411 | 471 | 524 | 572 | 617 | 697 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.1 | 223 | 328 | 400 | 464 | 520 | 568 | 614 | 696 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.15 | 150 | 290 | 375 | 340 | 503 | 556 | 605 | 692 | 805 | 875 | 980 | 1050 | 1400 | 1750 |
0.2 | — | 242 | 342 | 335 | 484 | 542 | 594 | 685 | 805 | 875 | 980 | 970 | 1365 | 1564 |
0.25 | — | — | 300 | 330 | 463 | 525 | 580 | 677 | 800 | 875 | 980 | 950 | 1350 | 1560 |
0.3 | — | — | 252 | 330 | 437 | 504 | 564 | 520 | 798 | 875 | 980 | 940 | 1300 | 1515 |
Flow Capacity Table for 100SN(m³/h)
Outlet Pressure (bar) |
Inlet Pressure (bar) | |||||||||||||
0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 1.0 | 1.3 | 1.5 | 1.8 | 2.0 | 3.0 | 4.0 | |
0.02 | 642 | 800 | 933 | 1049 | 1154 | 1249 | 1338 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.03 | 627 | 790 | 926 | 1043 | 1149 | 1246 | 1335 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.05 | 595 | 768 | 909 | 1031 | 1140 | 1239 | 1331 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.08 | 540 | 730 | 880 | 1010 | 1124 | 1227 | 1322 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.1 | 497 | 700 | 860 | 995 | 1112 | 1218 | 1316 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.15 | 360 | 623 | 800 | 950 | 1079 | 1192 | 1296 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.2 | — | 520 | 734 | 900 | 1039 | 1161 | 1272 | 1500 | 1725 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.25 | — | — | 649 | 838 | 992 | 1125 | 1243 | 1480 | 1718 | 1875 | 2100 | 2250 | 3000 | 3750 |
0.3 | — | — | 540 | 810 | 936 | 1081 | 1209 | 1460 | 1710 | 1875 | 2100 | 2250 | 3000 | 3750 |
Flow Capacity Table for 150SN(m³/h)
Outlet Pressure (bar) |
Inlet Pressure (bar) | |||||||||||||
0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 1.0 | 1.3 | 1.5 | 1.8 | 2.0 | 3.0 | 4.0 | |
0.02 | 1714 | 2137 | 2490 | 2798 | 3076 | 3330 | 3567 | 4000 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.03 | 1674 | 2110 | 2469 | 2783 | 3065 | 3322 | 3562 | 4000 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.05 | 1587 | 2050 | 2425 | 2750 | 3040 | 3304 | 3550 | 4000 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.08 | 1440 | 1950 | 2350 | 2694 | 2997 | 3273 | 3527 | 3987 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.1 | 1326 | 1876 | 2298 | 2653 | 2966 | 3249 | 3510 | 3980 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.15 | 959 | 1660 | 2145 | 2537 | 2877 | 3181 | 3458 | 3955 | 4600 | 5000 | 5600 | 6000 | 8000 | 10000 |
0.2 | — | 1385 | 1960 | 2400 | 2770 | 3098 | 3394 | 3919 | 4600 | 5000 | 5600 | 6000 | 8000 | 9000 |
0.25 | — | — | 1732 | 2236 | 2646 | 3000 | 3316 | 3873 | 4582 | 5000 | 5600 | 6000 | 7000 | 8000 |
0.3 | — | — | 1442 | 2040 | 2498 | 2884 | 3225 | 3815 | 4560 | 5000 | 5600 | 6000 | 6000 | 7000 |
The flow capacity table indicate the standard natural gas,which relative density is0.61. If the other medium,
the Parameters should be multiplied by the corresponding Parameters in the table coefficient.
Coefficient methane-1.05, ethane-0.76, butane-0.55, propane-0.63, air-0.78, nitrogen-0.79,
manufactured gas-1.17, carbon dioxide-0.63.
- Building Type Gas Regulator Box with doub
- Multipled gas regulator box/Regulator box
- Gas regulator for mesolow boiler/ Gas val
- Double lines gas regulator for boiler
- RTZ- ※/0.4A Series Direct-operated Gas
- RTJ-※/0.8GK Series Pressure Reducing Re
- RTJ- ※/0.4FK Series Self-operated Gas P
- RTZ-GQ Series Gas Pressure Regulator
- RTJ-SQ Series Gas Pressure Regulator
- RTZ-※/0.6 Type High-pressure Pipeline L
- What Is a Gas Regulator?
- How to Adjust a Gas Regulator
- How to Test a Fuel Injection Pressure Reg
- Gas Pressure Regulator Definition and Ope
- How Does a Natural Gas Pressure Regulator
- Compressed natural gas
- Pressure Regulators: Operation and Handli
- Compressed Gas Pressure Regulators
- How a Natural Gas Regulator Works?
- How Does a Natural Gas Regulator Work?
- CMR gas pressure regulator for dual-fuel
- Chinese Gas Pressure Reducing System Indu
- Oil and gas regulator chairman makes frac
- Gas Pressure Regulator Failure and Buildi
- CPC hopes for pipeline connection to Chin
- Dutch Gate LNG marks four months of reloa
- Ghana still waiting for gas-fired growth
- China’s SOE and gas price reforms pick
- DOE considers government control over LNG
- Angola LNG leases another tanker