Home > Accessories > Purification Equipment > XF Series Cyclone Dust Catcher

XF Series Cyclone Dust Catcher

DATE:2014-01-14 | comments: | posted by:liuailin

It is used in City Gates Stations,gas stations for filtrating gas and eliminating gas impurity.

Applicable medium

Natural gas, Manufactured gas, Liquefied petroleum gas,and other gases.

Technical Parameters

Design Pressure:16bar, 25bar, 40bar, 64bar
Work Pressure:10bar, 16 bar, 25bar, 40bar
Filtration Efficiency:≥90%
Temperature Capabilities:normal temperature

Caliber Dimensions

DN65, DN100, DN125, DN150, DN200, DN250

Type

XF-65-XF-150: hand hole operation,a leglike support
XF-200-XF-250:people hole operation,normal support

Selected Equipments

Pressure Difference Meter
Flange Cover Open Equipment
Safety Valve
Dirt Clean Valve

Overall Dimension

MODEL Inlet and Outlet
mm
DN×H

mm
H

mm
Emission size e
mm
Db
mm
 
XF-65 DN65 300×1700 1400 DN50 Φ282
XF-100 DN100 600×2500 2130 DN65 Φ583
XF-125 DN125 700×3000 2580 DN80 Φ689
XF-150 DN150 800×3300 2850 DN80 Φ792
XF-200 DN200 1200×3930 3350 DN100 Φ840
XF-250 DN250 1400×4330 3700 DN100 Φ1050

 
Hot Products
Hot Document
Hot news